Communication
2.2 Modbus
42 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
0267 a Phase angle a ° (degree)
0269 b Phase angle b ° (degree)
0271 c Phase angle c ° (degree)
0273 Phase angle ° (degree)
0275 f Power frequency Hz
0277 U
2
Neg. seq. comp. V %
0279 I
2
Neg. seq. comp. I %
0281 to 0292 - - -
0293 f (10 s) Frequency calculated every 10 s (internal) Hz
0295 THDS (Va) Voltage a THDS %
0297 THDS (Vb) Voltage b THDS %
0299 THDS (Vc) Voltage c THDS %
0301 THDS (Ia) Current a THDS %
0303 THDS (Ib) Current b THDS %
0305 THDS (Ic) Current c THDS %
0307 Voltage (12) Angle Va-Vb ° (degree)
0309 Voltage (31) Angle Vc-Va ° (degree)
0311 Current (12) Angle Ia-Ib ° (degree)
0313 Current (31) Angle Ic-Ia ° (degree)
0315 Q1a Reactive power (A)_Fundamental var
0317 Q1b Reactive power (B)_Fundamental var
0319 Q1c Reactive power (C)_Fundamental var
0321 Q1 Reactive power ()_Fundamental var
0323 to 0358 Flicker see chapter 2.2.7.18 -
0359 to 0382 - - -
0383 U
0
Zero seq. comp. V %
Table 2-21 Registers 0201 to 0390, and 6401 to 6484: Measured Values (cont.)
Register Type of Information Remark Unit
SYS_SICAM_Q100_US.book Page 42 Thursday, September 24, 2020 1:17 PM