Communication
2.2 Modbus
61SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.28 Registers 2201 to 2498: PQ Calculation for Maximum Harmonics - Voltage
Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
The data are calculated within the parameterized time (for example 30 s, 1 min etc.).
Data type: Measured value
2.2.7.29 Registers 2601 to 2898: PQ Calculation for Average Harmonics - Current
Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
The data are calculated within the parameterized time (for example 30 s, 1 min etc.).
Data type: Measured value
Table 2-36 Registers 2201 to 2498: PQ Calculation for Maximum Harmonics - Voltage Values
Register Type of Information Remark Unit
2201 H_Va/Vab-1_MAX
Harmonic (average value), voltage value, c-N, ca
(Fundamental)
V
2203 to
2298
H_Va/Vab-x_MAX
(x = 2 to 49)
Harmonic (average value), voltage value, c-N, ca
(2 bytes for each register)
V/%
2301 H_Vb/Vbc-1_MAX
Harmonic (average value), voltage value, b-N, bc
(Fundamental)
V
2301 to
2398
H_Vb/Vbc-x_MAX
(x = 2 to 49)
Harmonic (average value), voltage value, b-N, bc
(2 bytes for each register)
V/%
2401 H_Vc/Vca-1_MAX
Harmonic (average value), voltage value, c-N, ca
(Fundamental)
V
2403 to
2498
H_Vc/Vca-x_MAX
(x = 2 to 49)
Harmonic (average value), voltage value, c-N, ca
(2 bytes for each register)
V/%
Table 2-37 Registers 2601 to 2898: PQ Calculation for Average Harmonics - Current Values
Register Type of Information Remark Unit
2601 H_Ia-1_AVG
Harmonic (average value), current value, a
(Fundamental)
A
2603 to
2698
H_Ia-x_AVG
(x = 2 to 49)
Harmonic (average value), current value, a
(2 bytes for each register)
A
2701 H_Ib-1_AVG
Harmonic (average value), current value, b
(Fundamental)
A