Communication
2.2 Modbus
73SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.43 Registers 6801 to 6804: CO
2
Emissions (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
2.2.7.44 Registers 7001 to 7378: Prevailing Phase Angle of Harmonics – Voltage
Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Reference rate: Aggregation time
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
Table 2-53 Registers 6801 to 6804: CO
2
Emissions
Register Type of Information Unit
6801 CO
2
emissions of WP_imp t
6803 CO
2
emissions of WP_exp t
Table 2-54 Registers 7001 to 7378: Prevailing Phase Angle of Harmonics – Voltage Values
Register Type of Information Remark Unit
7001 HPP_Va-1
Harmonic (prev. phase angle), voltage value, a-N
(fundamental)
° (degree)
7003 to
7126
HPP_Va-x
(x = 2 to 63)
Harmonic (prev. phase angle), voltage value, a-N
(2 bytes for each register)
° (degree)
7127 HPP_Vb-1
Harmonic (prev. phase angle), voltage value, b-N
(fundamental)
° (degree)
7129 to
7252
HPP_Vb-x
(x = 2 to 63)
Harmonic (prev. phase angle), voltage value, b-N
(2 bytes for each register)
° (degree)
7253 HPP_Vc-1
Harmonic (prev. phase angle), voltage value, c-N
(fundamental)
° (degree)
7255 to
7378
HPP_Vc-x
(x = 2 to 63)
Harmonic (prev. phase angle), voltage value, c-N
(2 bytes for each register)
° (degree)
SYS_SICAM_Q100_US.book Page 73 Thursday, September 24, 2020 1:17 PM