Specifications
B-2
SIMATIC 505–2556 Installation and Operation Guide
Specifications (continued)
Table
B–1 Physical and Envir
onmental Specifications (continued)
Accuracy
T
ypes J, K, E, T
, L
T
ypes R,S
Millivolt
At a fixed ambient temperature between 0
_
C to
60_C
and
a reported temperature above 0
_
C for
types J, K, T
, L, E or above 500
_
C for types R and S
±0.5_
C at 25
_
±1_
C from 0
_
C to 60
_C
0_
C to full scale
±1_
F at 25
_
C
±2_
F from 0
_
C to 60
_C
32_
F to full scale
Reduced accuracy for measurements below 0
_
C to
32_F
±1_
C at 25
_
C for measurement range 500-1768
_C
±2_
C from 0
_
C to 60
_C
±2_
F at 25
_C
±4_
F from 0
_
C to 60
_C
Reduced accuracy for measurements below 500
_C
±
50
µ
V from 0
_
C to 60
_C
Common Rejection Mode
>130 db @ 50/60 Hz
Normal Rejection Mode
>180 db @ 60 Hz >80 db @ 50 Hz
Connector
48 position fixed, wire press in
W
ire Gauge
18 to 30 A
WG
Module Size
Single W
ide
Backplane Power Consumption
5 W
atts
Isolation
1500 VDC channel-to-channel
1500 VDC channel-to-backplane
Operaing T
emperature
0_
C to 60
_
C (32
_
F to 140
_F)
Storage T
emperature
–40_
C to 85
_
C (–40
_
F to 185
_F)
Humidity
, Relative
5% to 95% (non-condensing)
Agency Approvals
UL, UL for Canada
FM (Class
, Div 2), CE
Shipping W
eight
1.5 lbs. (0.68 kg)
Specifications subject to change without notice.