7.2 Connecting
BusAdapter
36 Equipment Manual, 08/2020, A5E41449003-AB
Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×LC:
Table 7- 1 PROFINET IO pin assignment with BusAdapter BA 2xLC
View
Signal name
Description
Receive Data
Transmit Data
Requirements
Prepare the IE FC FO cable with the IE FC FO LC plug connectors. For detailed instructions,
refer to the assembly instructions Preparing IE FC FO Cable with the plug-in connector IE
FC FO LC Plug (A5E36312721).
When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
IE FC FO Standard Cable GP (62.5/200/230): 70 mm
IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C): 88 mm
The maximum lengths of the fiber-optic cables are as follows:
IE FC FO Standard Cable GP (62.5/200/230): 2 km
IE FC FO Trailing Cable (62.5/200/230): 2 km
When the interface module is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter.