EasyManua.ls Logo

Siemens SIMATIC CP 340 - Page 108

Siemens SIMATIC CP 340
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication using function blocks
6.3 Using the function blocks for connecting to a communications processor
PtP coupling and configuration of CP 340
108 Manual, 04/2011, A5E00369892-03
Time Sequence Chart for P_SEND (FB 3)
The figure below illustrates the behavior of the DONE and ERROR parameters, depending
on how the REQ and R inputs are wired.
5(4
5
'21(
(5525
6HQGLQJUHTXHVW
7HUPLQDWLRQZLWKRXWHUURU
7UDQVIHU5(6(7
7UDQVIHU5(6(7
7HUPLQDWLRQZLWKRXWHUURU
5HTXHVWLV
QRWH[HFXWHG
6HQGLQJLV
WXUQHGRII
7HUPLQDWLRQZLWKHUURU
VWQWK6(1'SDUW
Figure 6-1 Time Sequence Chart for P_SEND (FB 3)
Note
The REQ input is edge-triggered. A positive edge at the REQ input is sufficient. The result of
the logic operation must not be at "1" at any point during transfer.

Table of Contents

Other manuals for Siemens SIMATIC CP 340

Related product manuals