Using ET 200SP higher than 2 000 m above sea level.
3.3 Restrictions
Product information on the documentation of the ET 200SP distributed I/O system
Product Information, 02/2021, A5E03799595-BG
75
3.3 Restrictions
Restrictions of the max. ambient temperature specified with regard to the installation altitude
Installation altitude
Derating factor for ambient temperature
1)
-1 000 to 2 000 m
1.0
2 000 to 3 000 m
0.9
3 000 to 4 000 m
0.8
4 000 to 5 000 m
0.7
1)
Base value for the application of the derating factor is the maximum permissible ambient tempera-
ture in °C for 2 000 m
Note
Linear interpolation between altitudes is permissible.
The derating factors compensate for the decreasing cooling effect of air at higher altitudes
due to lower density.
Note the mounting position of the respective module in the technical specifications. The
basis is the standard IEC 61131-2:2017.
Make sure that the power supplies you use are also rated for altitudes > 2 000 m.
The "Safety-related shutdown of standard modules" function, as described in the Internet
(
https://support.industry.siemens.com/cs/ww/en/view/39198632), is only approved up to
a maximum of 2 000 m.