C-3
Equipment
Manual OP7, OP17
Release 04/99
OP7 OP17
Interfaces
PP DP DP-12 PP DP DP-12
RS232 1 1 1 2 2 2
TTY 1 – 1 2 1 2
RS422/485 1 – 1 1 – 1
PPI/MPI/
PROFIBUS-DP
(up to 1.5 Mbd)/
RS422/485
– 1 1 – 1 1
PPI/MPI/
PROFIBUS-DP
(up to 12 Mbd)/
RS422/485
– – 1 – – 1
OP7 OP17
Ambient conditions
PP DP DP-12 PP DP DP-12
Operating temperature
– vertical installation
– horizontal installation
Transportation, storage
0 °C ... 50 °C
0 °C ... 35 °C
–25 °C ... 70 °C
Relative humidity
– operation
– transportation, storage
≤ 95% no dew
≤ 95%
Shock resistance
– operation
– transportation, storage
5 g/11 ms
25 g/6 ms
Vibration
– operation
– transportation, storage
0.075 mm(10 Hz ... 58 Hz)
1 g (58 Hz ... 500 Hz)
3.5 mm ( 5 Hz ... 12 Hz)
1 g (12 Hz ... 500 Hz)
Max. pressure difference
(front, rear)
2 hPa
Air pressure
– operation
– transportation, storage
706 ... 1030 hPa
581 ... 1030 hPa