Properties
1.1 IM151-1 HIGH FEATURE interface module (6ES7151-1BA02-0AB0)
IM151-1 HIGH FEATURE interface module (6ES7151-1BA02-0AB0)
Manual, 03/2008, A5E01075975-02
11
Status, interrupts, diagnostics
Interrupts yes
Diagnostic function yes
• Group error
Red "SF" LED
• PROFIBUS DP bus monitoring
Red "BF" LED
• Monitoring of the power supply voltage of the
electronics
Green "ON" LED
Updating the firmware for IM151-1 HIGH FEATURE
The IM151-1 HIGH FEATURE firmware can be updated using
STEP 7
V5.1, SP 3 or higher.
To update the firmware, you receive the *.UPD files containing the current firmware.
Requirements:
● The IM151-1 HIGH FEATURE in the station whose firmware is to be updated must be
accessible online.
● The files with the current firmware version must be available in the file system of your
programming device or PC.
Information regarding the method of procedure can be found in the
STEP 7
online help.
Note
Make sure to use the correct firmware version for the interface module in use during the
update process. An interface module with an older order number cannot be updated with the
firmware version for an interface module with a more recent order number and vise versa.
Configuration with more than 244 bytes of parameter data
For configurations with
STEP 7
V5.3 SP 3 and higher, it is possible to operate the IM151-1
HIGH FEATURE from 6ES7151-1BA01-0AB0 in DPV1 mode with more than 244 bytes of
parameter data.
A configuration based on the GSD file does not offer this possibility.
Note
If the parameter length is greater than 244 bytes, an increase in the station startup time is to
be expected.