10
Product information CP 3431
C79000Z8964C03805
Note
Read the sections about downloading configuration data to the CP in the
NCM S7 for Industrial Ethernet manual /8/.
1.4 Further Information on Operation
Downloading Firmware
The CP 343-1 supports firmware updates using the Firmware Loader.
An update of the firmware can be downloaded from the PC/programming de-
vice at any time. After downloading the firmware, the CPU must be reconfigu-
red (power off/on or memory reset).
For more information on downloading the firmware, refer to the README file
of the NCM S7 for Industrial Ethernet configuration software.
Note
Read the information on downloading a database to the CP in the
NCM S7 manual /8/.
Group status 8183 on the FC call interface
The return values DONE=0; ERROR=1; Status=8183 can be caused by the
following states:
S The CP is in the STOP mode.
S The connection is not configured.
S The connection is not established
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET CP 343-1 and is the answer not in the manual?

Siemens SIMATIC NET CP 343-1 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET CP 343-1
CategoryComputer Hardware
LanguageEnglish

Related product manuals