3 Technical Data
3.1 General Technical Data
Dimensions and Weight
Dimensions, module in casing H x W x D (mm) 125x80x120
Weight approx. 750 g
Voltage, Current, Operating Conditions
Power supply 5 V DC +/– 5%
24 V DC +/– 5%
Current consumption:
– from the S7-300 backplane bus:
– from the external 24 V supply:
70 mA
0.6 A.
Permitted ambient temperature
Specifications according to /7/ must be
adhered to when operating an S7-300 tier
– horizontal installation
– vertical installation 0 to 60° C
0 to 40° C
Altitude up to 3000m above sea level
All the information in /7/ in the Section ”General Technical Data” regarding the
following topics also applies to the CP 343-1:
S Electromagnetic compatibility
S Transportation and storage conditions
S Mechanical and climatic ambient conditions
S Insulation tests, class of protection and degree of protection