EasyManua.ls Logo

Siemens SIMATIC S7-1200 Easy Book - Page 100

Siemens SIMATIC S7-1200 Easy Book
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.1 General specifications
Easy Book
100 Manual, 05/2009, A5E02486774-01
Environmental Conditions - Operating
Ambient temperature range
(Inlet Air 25 mm below unit)
0° C to 55° C horizontal mounting
0° C to 45° C vertical mounting
95% non-condensing humidity
Atmospheric pressure 1080 to 795 hPa (Corresponding to an altitude of -1000
to 2000m)
Concentration of contaminants S0
2
: < 0.5 ppm; H
2
S: < 0.1 ppm; RH < 60% non-
condensing
EN 60068-2-14, Test Nb, temperature
change
5° C to 55°, 3° C/minute
EN 60068-2-27 Mechanical shock 15 G, 11 ms pulse, 6 shocks in each of 3 axis
EN 60068-2-6 Sinusoidal vibration DIN rail mount: 3.5mm from 5-9 Hz, 1G from 9 - 150 Hz
Panel Mount: 7.00mm from 5-9 Hz, 2G from 9 to 150 Hz
10 sweeps each axis, 1 octave per minute
High Potential Isolation Test
24 V/5 V nominal circuits
115/230 V circuits to ground
115/230 V circuits to 115/230 V circuits
115 V/230V circuits to 24 V/5 V circuits
520 VDC (type test of optical isolation boundaries)
1,500 VAC routine test/1950 VDC type test
1,500 VAC routine test/1950 VDC type test
1,500 VAC routine test/3250 VDC type test
Protection Class: Protection Class II according to EN 61131-2 (Protective conductor not
required)
Degree of protection
IP20 Mechanical Protection, EN 60529
Protects against finger contact with high voltage as tested by standard probe. External
protection required for dust, dirt, water and foreign objects of < 12.5mm in diameter.
Rated voltages
Rated Voltage Tolerance
24 VDC 20.4 VDC to 28.8 VDC
120/230 VAC 85 VAC to 264 VAC, 47 to 63 Hz
NOTICE
When a mechanical contact turns on output power to the S7-1200 CPU, or any digital
signal module, it sends a "1" signal to the digital outputs for approximately 50
microseconds. You must plan for this, especially if you are using devices which respond to
short duration pulses.