Online functionality
8.4 Uploading from the online CPU
Easy Book
92 Manual, 05/2009, A5E02486774-01
8.4 Uploading from the online CPU
Uploading the code blocks from an online CPU
STEP 7 provides two methods for uploading the code blocks of the user program from an
online CPU.
Using the Project navigation, you can drag and drop the code blocks from
the online CPU to a CPU in your off-line project.
1. With your project open, expand the "Online access" container and
select an online CPU.
2. Expand the online CPU to display the code blocks of the user program.
3. Drag the code blocks from the online CPU to the "Program blocks"
container of the CPU in your offline project.
STEP 7 Basic copies the code blocks from the online CPU to your offline
project.
You can also use the "Compare" function to synchronize the code
blocks between the online CPU and the offline CPU:
1. Select the online CPU.
2. Select the "Compare offline/online" command from the "Tools"
menu.
If the code blocks of the offline do not match the code blocks of the
online CPU, the "Compare" editor allows you to synchronize the two
CPU.
Clicking the "Synchronize"
button uploads the code
blocks to the offlineCPU.