6 Device Code and Address Code
Use device code and address code when you set "Device Type & Address" for the address type of the data display
or other devices.
6.1 S7-200 Series
6.2 S7-300/400 Series
Device
Device Name
Device Code
(HEX)
Address Code
English German
Variables V V 0001 Value of word address divided by 2
Input I E 0080 Value of word address divided by 2
Output Q A 0081 Value of word address divided by 2
Internal Marker M M 0082 Value of word address divided by 2
Timer T T 0060 Word Address
Counter C Z 0061 Word Address
Device
Device Name
Device Code
(HEX)
Address Code
English German
Data Block DB DB 0000
(Data Block No. x 0x10000) +
Value of (word address divided by 2)
Input I E 0080 Value of word address divided by 2
Output Q A 0081 Value of word address divided by 2
Internal Marker M M 0082 Value of word address divided by 2
Timer T T 0060 Word Address
Counter C Z 0061 Word Address