Properties / services
1.4 Other services
CP 343-1 Lean
14 Equipment Manual, 01/2023, C79000−G8976−C198−09
1.4 Other services
The CP also provides the following additional services:
Media redundancy (MRP)
Within an Ethernet network with a ring topology, the CP supports the media redundancy
protocol MRP. You can assign the role of MRP client to the CP.
Time-of-day synchronization over Industrial Ethernet
Time-of-day synchronization can be configured in the following modes:
SIMATIC mode
The CP receives MMS time messages and synchronizes its local time and the time of
the CPU.
Accuracy approx. +/- 1 second
You can choose whether or not the time of day is forwarded. The forwarding direction
can also be selected (station > LAN or LAN > station).
or
NTP mode (NTP: Network Time Protocol)
The CP sends timeofday queries at regular intervals to an NTP server and synchronizes
its local time of day. The forwarding of the time-of-day to the CPU is optional.
Accuracy approx. +/- 1 second
Addressing using a factoryset MAC address
The CP can be reached via the default MAC address to allow an IP address to be assigned.
SNMP agent
The CP supports data queries over SNMP in version V1 (Simple Network Management
Protocol). It delivers the content of certain MIB objects according to the MIB II standard,
LLDP MIB, Automation System MIB and MRP Monitoring MIB.
Module access protection
To protect the module from accidental or unauthorized access, protection can be
configured at various levels.
IP configuration
For the PROFINET interface, you can configure how and with which method the CP is
assigned the IP address, the subnet mask and the address of a gateway.
As an alternative to STEP 7, you have the option of assigning the connection configuration
via a block interface in the user program (FB55: IP_CONFIG).

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)