Performance data
2.6 Characteristic data of the integrated switch
CP 343-1 Lean
Equipment Manual, 01/2023, C79000−G8976−C198−09
21
Execution times of the FC blocks PNIO_SEND / PNIO_RECV
The execution time required to process the function blocks (PNIO_SEND, PNIO_RECV)
required on the S7-300 CPU is decisive for the calculation of the reaction times in PROFINET
IO.
Note
Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET
networks for a series of configurations can be found on the Internet at the following address:
Link: (
http://support.automation.siemens.com/WW/view/en/25209605)
2.6 Characteristic data of the integrated switch
Learning addresses / deleting addresses (aging time)
The switch integrated in the CP (PROFINET interface) reads the source addresses included in
the data packets. The switch therefore learns the addresses of the end devices connected via
a port.
If the switch receives a data packet, it directs this packet only to the port via which the
appropriate end node can be reached.
The switch monitors the age of the learned addresses. Addresses that exceed the "aging time"
are deleted. The aging time is 5 minutes.
Ports can be deactivated individually
The ports of the switch integrated in the CP can be deactivated individually in STEP 7 /
HW Config. This can, for example, be used for service purposes.
To do this, open the properties dialog of the relevant port and select the "disabled" setting
under "Options > Transfer medium / duplex".
The port is turned off completely when it is disabled. The corresponding LED on the device
(for example X1P1) is then turned off.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals