Performance data
2.4 Characteristic data of the SEND/RECEIVE Interface
CP 343-1 Lean
Equipment Manual, 01/2023, C79000−G8976−C198−09
19
2.4 Characteristic data of the SEND/RECEIVE Interface
The SEND/RECEIVE interface provides access to communication over TCP, ISOonTCP and UDP
connections.
The following characteristics are important:
Table 2- 3 Characteristic data of the SEND/RECEIVE Interface
Characteristic
Explanation / values
Number of ISO-on-TCP connections + TCP
connections + UDP connections in total
8 maximum
Notes:
All UDP connections are also possible in
multicast mode.
Free UDP connections are supported by the
CP.
Maximum data length for the blocks AG_SEND (as
of V4.0) and AG_RECV (as of V4.0)
AG_SEND and AG_RECV allow the transfer of
blocks of data with the following length:
1 to 8192 bytes for ISO-on-TCP, TCP;
1 to 2048 bytes for UDP.
Restrictions for UDP
Transfer is not confirmed
The transmission of UDP frames is unconfirmed,
in other words the loss of messages is not
detected or displayed by the send block
(AG_SEND).
No receipt of UDP broadcast
To avoid communications overload of the CP due
to high broadcast load, the CP does not allow
receipt of UDP broadcasts.
UDP frame buffering
Size of the frame buffer with buffering enabled: 2
Kbytes
Note:
Following a buffer overflow, newly arriving
frames are discarded.
Execution times of the FCs AG_SEND / AG_RECV
The execution time required to process the FC blocks (AG_SEND, AG_RECV) required on the
S7-300 / C7-300 CPU is decisive for the calculation of the CPU cycle times (OB1) for
SEND/RECEIVE connections.
Note
Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET
networks for a series of configurations can be found on the Internet at the following address:
Link: (http://support.automation.siemens.com/WW/view/en/25209605)

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals