EasyManua.ls Logo

Siemens SIMEAS R - Mass Storage; General

Siemens SIMEAS R
102 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81Digital Fault Recorder, SIMEAS R/SIMEAS R-PMU, Maintenance Manual
E50417-H1074-C364-A2, Release 11.2009
Mass Storage 3
3.1 General
Log File
In the course of maintenance work, the system messages of the device should be regularly read
out using the OSCOP P "Transfer" module (log file).
If the log file contains entries with the contents: "Self-monitoring: Fatal checksum error", the device has
detected an error on the mass storage. In this case, the mass storage must be replaced immediately!
Mass storage versions
Depending on the production date, the CPU board of the device can be equipped with a 2.5"
flash disk (7KE6x00-3HCx) or with a DiskOnModule-(DOM) flash memory (7KE6x00-3HCx/CC).
Figure 3-1 2.5” flash disk (left) and DOM flash memory (right)
Note
For a detailed description of "Transferring log file", please refer to the chapter "Transferring data"
in the OSCOP manual, order no. E50417-H1076-C170.

Other manuals for Siemens SIMEAS R

Related product manuals