EasyManua.ls Logo

Siemens SIMOTION C240 - Interfaces; SIMOTION C interfaces

Siemens SIMOTION C240
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIMOTION C
Operating Instructions, 02/2012
35
Interfaces
3
3.1 SIMOTION C interfaces
The interfaces and their meaning are described in following table.
Table 3- 1 Interfaces
Interfaces Description
Bus connector Rear-mounted connector for connecting to other S7 modules via the
I/O bus
Drive interface (onboard)
(C230-2, C240)
50-pin Sub-D connector X2 for the analog connection of analog and
stepper drives (max. 4 axes)
Measuring system interface
(onboard) (C230-2, C240)
15-pin Sub-D sockets X3 to X6 for connection of encoders (max. 4)
I/O interface 40-pin front connectors X1 for connecting the fast digital inputs/digital
outputs including measuring inputs and external zero mark and for
wiring the READY relay
Power supply connection 4-pin screw-type terminal connection X10 for connecting the 24 V
load power supply
Memory module slot Slot for micro memory card (MMC)
PROFIBUS DP1 interface 9-pin Sub-D socket X8 for connection to the PROFIBUS DP. This
interface can be used for isochronous operation
PROFIBUS DP2/MPI
interface
9-pin Sub-D socket X9 for connection to PROFIBUS DP (factory
setting) or an MPI bus
This interface can be used for isochronous operation.
Ethernet interface 8-pin RJ45 socket X7 for connection to an Industrial Ethernet
PROFINET interface with
three ports (C240 PN)
3 x 8-pin RJ45 sockets X11 P1, X11 P2 and X11 P3 for connecting to
PROFINET subnets