Climatic ambient conditions
SIMOTION D410 may not be used under the following climatic ambient conditions:
Note
Observe the application ranges of the PM340 power modules along with their derating. For
further information, see SINAMICS documentation.
Table 7-18 Climatic ambient conditions
Ambient conditions Application range Remarks
Permissible ambient
temperature for operation
0 to +55 °C Oil mist, ice formation, moisture condensation,
dripping water, spraying water, splashing water
and
water jets are not permitted (EN 60204, Part
1)
Maximum installation
altitude
2000 m to max. 5000 m above sea level From an altitude of 2000 m, the maximum
ambient temperature decreases by 7°C every
1000 m.
Relative humidity 5 to 95 % Without condensation, corresponds to a relative
humidity (RH) severity level 2 according to
IEC 1131‑2
Air pressure 795 to 1080 hPa -
Pollution degree 2 acc. to EN 60664-1 -
Pollutant concentrations Substances:
SO
2
: <0.5 ppm;
Relative humidity <60 %, no condensation
H
2
S: <0.1 ppm;
Relative humidity <60 %, no condensation
Test:
10 ppm 4 days
1 ppm; 4 days
Technical data
7.8 Mechanical and climatic ambient conditions
SIMOTION D410
94 Manual, 04/2014

Table of Contents

Other manuals for Siemens SIMOTION D410 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D410 DP and is the answer not in the manual?

Siemens SIMOTION D410 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D410 DP
CategoryControl Unit
LanguageEnglish

Related product manuals