Commissioning (software)
6.5 Additional information on configuring the SINAMICS Integrated
SIMOTION D4x5-2
220 Commissioning and Hardware Installation Manual, 02/2012
If an error is detected during the execution of a parameter job, the error cause is signaled via
the parameter itself (no message via the fault buffer).
Causes of errors for parameter jobs
Table 6- 7 Causes of errors of the parameter jobs
Value Cause
10 Error occurred while deleting
11 No backup possible: Memory card is not inserted
12 No backup possible: Memory card is full
13 Backup could not be completed (e.g. memory card removed during the backup)
14 Restoration not possible: Memory card is not inserted
15 Restoration not possible: Checksum of the NVRAM data backup file is faulty
16 Restoration not possible: No backup available
Note
The memory card must be always remain inserted for SIMOTION D; please refer to the
SINAMICS manuals for which SINAMICS control units allow the memory card to be
removed.
Parameter p7775 is only reset automatically to 0 after the successful completion of a job.
Know-how and write protection
Parameter p7775 is not part of the know-how protection.
I.e. the parameter can be read and written irrespective of the know-how.
Parameter p7775 is part of the write protection. This means the parameter can only be
written by the controller that configured a PZD cyclic communication with the SINAMICS
when write protection is activated (p7761 = 1).
All other write jobs are acknowledged negatively, e.g.
SCOUT/STARTER
For SINAMICS CUs, BOP, IOP, AOP
Other masters that only communicate acyclically with the SINAMICS