EasyManua.ls Logo

Siemens SIMOTION D425-2

Siemens SIMOTION D425-2
394 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting
3.7 Connecting PROFIBUS/MPI
SIMOTION D4x5-2
64 Commissioning and Hardware Installation Manual, 02/2012
3.7.2 PROFIBUS cables and connectors
Properties of PROFIBUS cables
The PROFIBUS cable is a two-core, twisted and shielded cable with defined properties:
Properties of the cables
Table 3- 4 Properties of PROFIBUS cables
Characteristics Values
Characteristic impedance Approximately 135 to 160 Ω (f = 3 to 20 MHz)
Loop resistance ≤ 115 Ω/km
Effective capacitance 30 nF/km
Damping 0.9 dB/100 m (f = 200 kHz)
Permissible conductor cross-section 0.3 mm
2
to 0.5 mm
2
Permissible cable diameter 8 mm + 0.5 mm
Connector features
The bus connector is used to connect the PROFIBUS cable to the PROFIBUS DP interfaces
(X126, X136), thus establishing a connection to additional nodes.
Only bus connectors with a 35° cable outlet should be used in order to ensure that the front
cover can be closed.
See also
SIMOTION D4x5-2
Manual, Section "Spare parts and accessories which can be ordered"