Connecting
3.9 Connecting PROFINET IO components
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
75
Mixed operation of IRT and RT
For mixed operation of IRT and RT, note that the IRT-capable devices must form a so-called
IRT domain, i.e. there must not be any non-IRT devices on the data transmission link
between the IRT devices.
Figure 3-15 Mixed operation of IRT and RT
3.9.2 PROFINET cables and connectors
Cable and connector types
Note
For connecting PROFINET IO to D4x5-2, a connector with a 145° cable outlet is
recommended (IE FC RJ45 plug 145).
Figure 3-16 RJ45 PN connector with a 145°cable outlet