EasyManua.ls Logo

Siemens SIMOVERT MASTERDRIVES 6SE70 VC - Basic Start-Up

Siemens SIMOVERT MASTERDRIVES 6SE70 VC
57 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Version 1.0 March 1, 2000 Page 41
2.2 Basic Start-up (Regenerative Rectifier without
Autotransformer)
P051 = 2
P053 = 6
P052 = 5
P071 = 460
P320 = 20
P773 = 1.00
P051=2
Select “Basic Mode Settings”
P053 =6 Access Parameter
P052 = 5
Drive Settings
P071 = Input Rectifier Voltage
Generally = 460 Volt
P320 = 20
Smooth Load Amps, to
prevent input line sags
from effecting the DC BUS
regulator
P773= 1.00
Deadband Converter, to
prevent “toggling” between
Regen and Rectifier
bridges.

Related product manuals