Parameterization 06.2006
6SE7087-6KP50 Siemens AG
8-48 Operating Instructions SIMOVERT MASTERDRIVES
Input in
P097
Motor order
number
(MPRD)
Rated
speed
n
n
[rpm]
Pole pair
number
Z
p
Current
I
n
[A]
Voltage
U
n
[V]
Torque
M
n
[Nm]
Frequency
f
n
[Hz]
67 1PH4135-4_F 1500 2 51.2 350 140 51.6
68 1PH4137-4_F 1500 2 60.5 350 172 51.6
69 1PH4163-4_F 1500 2 86.3 350 236 50.9
70 1PH4167-4_F 1500 2 103.3 350 293 51.0
71 1PH4168-4_F 1500 2 113.0 350 331 51.0
72 1PH7107-2_G 2300 2 24.8 398 50 78.6
73 1PH7167-2_G 2000 2 88.8 350 196 67.4
74 to 99 for future applications
100 1PL6284-..D. 1150 2 478.0 400 2325 38.9
101 to
253
for future applications
Table 8-6 Motor list 1PH7 / 1PL6 / 1PH4
For information about motor ratings and availability please see Catalog
DA65.3 "Synchronous and asynchronous servomotors for SIMOVERT
MASTERDRIVES".
The data stored under the motor numbers describe the design point of
the motor. In Chapter 3 "Induction servo motors" of Catalog DA65.3 two
operating points are indicated for operation with MASTERDRIVES MC.
The operating points are calculated for 400 V and 480 V AC line
voltage on the converter input side.
The data for the 480 V line voltage are stored in the control system as
the rated motor current is slightly lower for a few motors in this
operating point.
P293 "Field weakening frequency" is always decisive for the actual field
weakening operating point. The field weakening frequency P293 is
automatically calculated for a line voltage of 400 V.