Faults and Alarms 10.99
6SE7087-6KP50 Siemens AG
12-4 Operating Instructions SIMOVERT MASTERDRIVES
Number / Fault Cause Counter-measure
F045
HW fault on optional
boards
A hardware fault has occurred during access
to an optional board.
- Replace CU board (Compact, chassis units)
- Replace the unit (Compact PLUS)
- Check the connection betewen the subrack
and the optional boards
- Replace optional boards.
F046
Parameter coupling
fault
A fault has occurred during the transfer of
parameters to the DSP.
If fault re-occurs, replace the board/unit