Commissioning   
5.10 Start-up and Swap Behavior of the Inverter 
  Control Units CU240S 
118  Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD 
PM Swap (CU externally powered) - MMC with valid Parameter set plugged 
●  Swap detected, Parameter MMC -> RAM, inverter runs into F00395 
 
CAUTION 
 
 
If the parameter download MMC -> RAM fails, one of the following faults will be 
generated: F0061, F0062, F0063 or F0064, details see parameter list. 
●  With confirming F00395 RAM values will be written to the EEPROM and with a standard 
CU operation is possible, in case of a fail-safe CU an acceptance test is required. 
PM Swap (CU externally powered) - no MMC plugged 
●  Swap detected, Parameter EEPROM -> RAM, inverter runs into F00395 
●  If the parameters, already held in the EEPROM are ok there is no commissioning 
necessary. 
●  Confirmation for standard CU or acceptance test in case of fail-safe CU required 
 
 
 
Note 
After a PM Swap without MMC the parameter settings only stored in RAM will be lost. 
Rules regarding a swap  
 
 
Note 
F00395 cannot be cleared via power cycle.  
F00061, F00062, F00063 and F00064 can only be cleared via power cycle. 
 
There are a number of scenarios where a swap is allowed, each with their own unique set of 
conditions that must be observed. 
 
DANGER 
 
Do not attempt to hot swap a power module (PM) 
Before attempting to swap a PM it must be fully powered-down. Any attempt to swap-out a 
PM when power is still applied could result in death of personnel and severe damage to 
property and equipment. 
WARNING 
 
Swap restrictions 
Before performing a swap it is the responsibility of the user to ensure that: 
•  only CUs of the same type are swapped 
•  the MMC contains a valid parameter set (a valid parameter set means, it is not from a 
different type of CU e.g. CU240S DP and CU240S or fail-safe and standard CUs) 
•  only PMs of the same type and power rating are swapped. 
•  the application is in a safe state before any swap of equipment is performed.