Operation 
  7.2 Operation States Displayed via LED 
Control Units CU240S 
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD 
191 
Behavior of the status LED  
 
  CU240S  CU240S 
DP  
CU240S 
DP-F 
CU240S 
PN 
CU240S 
PN-F 
System-Fault (SF) 
•  ON: A general system error either software or hardware 
related is indicated. 
•  Flashing: Download from MMC runs 
x  x  x  x  x 
Ready (RDY) 
•  ON: The inverter is ready to run or running. 
•  Flashing: Commissioning or download from MMC runs 
x  x  x  x  x 
Bus-Failure (BF) 
•  ON: Bus failure, no connection to the DP-Master / 
PROFInet I/O controller (searching for baud rate) 
A bus failure is defined as signaling problem on the bus 
itself.  
Faults according to the inner data structure of the 
transmitted communication frames (e.g. CRC check of 
PROFIsafe telegram) are not denoted as bus failure. Such 
failures are indicated by the SF LED. 
•  Flashing: I/O device is not configured or is wrongly 
configured (baud rate found, no data exchange). 
 x x x x 
Link-established (LNK) 
•  ON: Link established 
•  OFF: No link established 
      x  x 
RX/TX (ACT) 
•  ON: Data transfer 
•  OFF: No data tansfer 
      x  x 
End-state (ES) 
•  ON: The end state of a triggered fail-safe function (flashing 
LED) has been reached. 
•  Flashing: Safety commissioning or download  
 from MMC runs 
    x    x 
Safe Torque Off (STO) 
Safe Stop 1 (SS1)  
Safely-Limited Speed (SLS) 
•  ON: Function parameterized 
•  Flashing: Activated 
•  All Safety LEDs flashing: Safety commissioning or 
download from MMC runs 
•  Flashing and LED ES ON: End state reached 
    x    x