Commissioning   
5.5 Commissioning using the BOP 
  Control Units CU240S 
88  Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD 
Safely-limited Speed 
 
Parameter  Description  Unit  Default   Min.  Max. 
P9690  SI setpoint for SLS 
Speed setpoint that is used when the safely limited speed (SLS) is 
selected. Depending on the setting in P9692/P9892 the frequency of 
P9690/P9890 may also serve as a speed threshold instead of a 
setpoint (see P9692). 
Note: 
For applications with changing loads, an increase of P9680/P9880 or 
P9691/P9891 is recommended. If the "safely limited speed" (SLS) is 
selected while the output frequency is below the setpoint value, Bit 04 
and Bit 05 will be set simultanously in r9772. 
Hz  10.0  2.0  300.0 
P9890  SI setpoint for SLS 
Refer to P9690. 
kHz  0.010  0.002  0.300 
P9691  SI tolerance for SLS 
Upper tolerance margin for the SLS. If the output frequency at 
initiation of the safely limited speed lies below the value of 
P9691/P9891 and later on exceeds that value an LSTO is generated. 
The tolerance defined by the difference P9691 to P9690 (or P9891 to 
P9890) is also used for the monitoring ramp when the SBR is active. 
For applications with changing loads it is recommended to increase 
P9691/P9891. 
Note: 
The value in P9691 needs to be larger than the value in P9690. This 
condition is checked when leaving the safety commissioning. 
Hz  13.0  5.0  302.0 
P9891  SI tolerance for SLS 
Refer to P9691. 
kHz  0.013  0.005  0.302 
P9692  SI response to selecting SLS 
Response if, after initiation of safely limited speed (SLS), the speed 
exceeds the limiting values: 
•  SLS mode 0: Activation of the speed monitoring and disabling the 
set value channel. If the output frequency at initiation of SLS 
exceeds the parameterized speed limit an LSTO is initiated. If the 
output frequency falls below the accuracy limit (1 Hz) an STO is 
triggered. 
•  SLS mode 1: Braking to the set speed with safe braking ramp, then 
activation of the monitoring function and disabling the set value 
channel. If the output frequency falls below the accuracy limit (1 
Hz) an STO is triggered. 
•  SLS mode 2 
The monitoring is activated at once. If the output frequency at 
initiation of SLS exceeds the parameterized speed limit an LSTO is 
initiated. The set value channel is not disabled. If the output 
frequency falls below the accuracy limit (1 Hz) an STO is triggered.
•  SLS mode 3 
Like SLS mode 2 except the following: If the output frequency falls 
below the accuracy limit (1 Hz) the inverter stays in operational 
state for 5 s. Within this five seconds reversing or speed up again 
is possible. 
-  1  0  2 
P9892  SI response to selecting SLS 
Refer to P9692. 
-  1  0  2