12-pulse series connection
4.3 Commissioning
12-pulse applications
Compact User Manual, 09/2015, A5E34871844H
39
Table 4- 3 For 12-pulse series connection of SINAMICS DCM converters with an uncontrolled rectifier:
Parameter
Master
Parallel units
p51798 Voltage on the uncontrolled rectifier Application-specific (50 % -
100 %)
The same as on the master
p51799 Mode of operation 0 0
p51800 Position in the topology 45 (master for diode rectifi-
er)
43
p51807 Telegram failure time 0.0 s
0.1 s if devices connected
in parallel are available
0.1 s
p51801
Amount of send data
0,4,8,12,16
The same as at the master
p51802
Number of power units
1)
≥ 2
≥ 2
p51803
n+m mode
0 or 1
The same as at the master
p51804[..]
Send data
Application-specific
The same as at the master
p51805
Bus terminator
0 or 1
2)
0 or 1
2)
p51806
Station address
Unique address (1..16)
The same as at the master
p51807
Telegram failure time
Recommended, 0.1 s
Recommended, 0.1 s
p50082
Field operating mode
≠ 0 (application-specific)
0 (no field)
p50076[..] Reduction in the rated unit DC cur-
rent
3)
Application-specific The same as on the master
p50078[..]
Rated value for supply voltage
Application-specific
The same as on the master
p50100 Rated motor current Rated motor cur-
rent/number of SINAMICS
DCMs
The same as on the master
p50165
Enable torque direction change
0 or 1
4)
The same as at the master
1)
If the number of power units that are ready to operate for n+m operation is less than the value set in p51802, then fault
message F60044 is output, followed by shutdown (OFF2).
2)
= 1 at the two outermost units (= at the physical ends of the bus line)
= 0 on all of the other units
3)
Note: In conjunction with r50072[..], ensure that p50076[..] is correctly set, as described in the List Manual under
p50076[..].
4)
For 4Q units, it is imperative that the torque direction change is inhibited:
0 = M0 or MII; 1 = M0 or MI

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals