Technical specifications
Power Module PM240
72 Hardware Installation Manual, 07/2009, A5E00807525B AD
Table 6- 6 Frame Sizes C, 3 AC 380 V … 480 V, ± 10%
filtered 0BE25-5AA0 0BE27-5AA0 0BE31-1AA0
Order No.
unfiltered
6SL3224-
0BE25-5UA0 0BE27-5UA0 0BE31-1UA0
kW 5.5 7.5 11 Rated power based on HO-
loading
hp 7.5 10 15
Power loss kW 0.240 0.297 0.396
Rated input current (HO) A 16.7 23.7 32.7
Rated output current (HO) A 13.2 19 26
Rated input current (LO) A 21.9 31.5 39.4
Rated output current (LO) A 18 25 32
Fuse A 20 32 35
l/s 55 55 55 Required cooling air flow
CFM 120 120 120
mm
2
4.0 … 10 4.0 … 10 4.0 … 10 Input cable /
Output cable
AWG 12 … 8 12 … 8 12 … 8
kg 6.5 6.5 6.5 Weight filtered/
unfiltered
lb 14.3 14.3 14.3
Table 6- 7 Frame Sizes D, 3 AC 380 V … 480 V, ± 10%
filtered 0BE31-5AA0 0BE31-8AA0 0BE32-2AA0
Order No.
unfiltered
6SL3224-
0BE31-5UA0 0BE31-8UA0 0BE32-2UA0
kW 15 18.5 22 Rated power based on HO-
loading
hp 20 25 30
filtered kW 0.44 0.55 0.72 Power loss
unfiltered kW 0.42 0.52 0.69
Rated input current (HO) A 40 46 56
Rated output current (HO) A 32 38 45
Rated input current (LO) A 46 53 72
Rated output current (LO) A 38 45 60
Fuse A 50 63 80
l/s 55 55 55 Required cooling air flow
CFM 120 120 120
mm
2
10 … 35.0 10 … 35.0 10 … 35.0 Input cable /
Output cable
AWG 7 … 2 7 … 2 7 … 2
kg 16 16 16 filtered
lb 35.3 35.3 35.3
kg 13 13 13
Weight
unfiltered
lb 28.7 28.7 28.7