EasyManua.ls Logo

Siemens SINAMICS G120 - Page 27

Siemens SINAMICS G120
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
4.3 Connecting the inverter to the fieldbus
CU240B-2 and CU240E-2 Control Units
Compact Operating Instructions, 04/2015, A5E35792002B AA
27
Examples for telegrams via PROFIBUS and PROFINET
Telegram 1:
STW1
Control word 1
ZSW1
Status word 1
PZD01/02
Process data 16-bit
NSOLL_A
Speed setpoint
NIST_A
Speed actual value
Control word 1 (STW1), PZD receive word 1 (word: r2050[0], bits: r2090.00 … r2090.15)
Bit
Meaning
Explanation
0 0 = OFF1 The motor brakes with the ramp-down time p1121 of the ramp-function generator.
The inverter switches off the motor at standstill.
0 → 1 = ON The inverter goes into the "ready" state. If, in addition bit 3 = 1, then the inverter
switches on the motor.
1
0 = OFF2
Switch off the motor immediately, the motor then coasts down to a standstill.
1 = No OFF2
Precondition in order to be able to switch on the motor using bit 0 (ON command).
2
0 = Quick stop (OFF3)
The motor brakes with the OFF3 ramp-down time p1135 down to standstill.
1 = No quick stop (OFF3)
Precondition in order to be able to switch on the motor using bit 0 (ON command).
3
0 = Inhibit operation
Switch off the motor immediately → motor coasts down to a standstill.
1 = Enable operation
Precondition in order to be able to switch on the motor using bit 0 (ON command).
4
0 = Disable RFG
The inverter immediately sets its ramp-function generator output to 0.
1 = Do not disable RFG
The ramp-function generator can be enabled.
5
0 = Stop RFG
The output of the ramp-function generator stops at the actual value.
1 = Enable RFG
The output of the ramp-function generator follows the setpoint.
6 0 = Inhibit setpoint The inverter brakes the motor with the ramp-down time p1121 of the ramp-function
generator.
1 = Enable setpoint Motor accelerates with the ramp-up time p1120 to the setpoint.
7 0 → 1 = Acknowledge faults Acknowledge fault. If the ON command is still active (bit 0 = 1), the inverter
switches to "closing lockout" state.
8, 9 Reserved
10
0 = No control via PLC
The inverter ignores the process data from the fieldbus.
1 = Control via PLC
Control via fieldbus, the inverter accepts the process data from the fieldbus.
11
1 = Direction reversal
Invert setpoint in the inverter.
12
Not used
13
1 = MOP up
Increase the setpoint saved in the motorized potentiometer.
14
1 = MOP down
Reduce the setpoint saved in the motorized potentiometer.
15 Reserved Changes over between settings for different operation interfaces (command data
sets).

Other manuals for Siemens SINAMICS G120

Related product manuals