Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C converter
32 Getting Started, 04/2014, FW V4.7, A5E34264105B AA
6.
Transfer the data from the motor rating plate to the inverter:
6.1.
Motor standard
KW 50HZ
IEC
HP 60HZ
NEMA
KW 60HZ
IEC 60 Hz
6.2.
Rated
voltage
6.3.
Rated current
6.4.
IEC power (kW)
NEMA (HP)
6.5.
Rated speed
7.
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
No measurement of motor data.
STIL ROT
Recommended setting: Measure the motor data at
standstill and with the motor rotating.
STILL
Measure the motor data at standstill.
Select this setting if one of the following cases is
applicable:
You have selected the control mode "SPD N EN".
However, the motor cannot rotate freely
for example,
if the traversing range is mechanically limited.
You have selected V/f control as a control mode, e.g.
"VF LIN" or "VF QUAD".
ROT
Measuring the motor data while it is rotating.
8.
Select the default setting for the interfaces of the inverter that is
suitable for your application. You will find the default settings in
Section: Default settings of the terminals (Page 25).
9.
Set the minimum speed of the motor.