Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
35
4.2.2
Selecting the control mode
Criteria for selecting either V/f control or vector control
U/f control or FCC (flux current control)
Vector control without an encoder
Application
examples
Pumps, fans, and compressors with flow
characteristic
Wet or dry blasting technology
Mills, mixers, kneaders, crushers, agitators
Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
Basic spindles
Pumps and compressors with displacement
machines
Rotary furnaces
Extruder
Centrifuge
Motors that can be
operated
The rated current of the motor must lie in the range of 13 %100 % of the rated current of the
inverter.
Properties of
closed-loop motor
control
The closed-loop control is insensitive to
inaccurate motor data settings, e.g. the
motor temperature
Can be commissioned with just a few
settings.
Responds to speed changes with a typical
settling time of 100 ms200 ms
Responds to load surges with a typical
settling time of 500 ms
U/f and FCC are suitable for the following
cases:
For power-up times 0 rated speed >
2 s
For applications with increasing load
torque without load impulses
The vector control makes highly efficient use of
the power module, the motor and the
mechanical system (95% of the line voltage).
The vector control responds to speed changes
with a typical settling time of < 100 ms.
The vector control responds to load impulses
with a typical settling time of 20 ms.
The vector control is required in the following
cases:
For power-up times 0 rated speed < 2 s
For applications with fast and high load
impulses
For heavy duty starting using ≤ 90 % of the
stall torque of the motor
Vector control typically achieves a torque
accuracy of ± 5 % for 10 % … 100 % of the
rated speed
Max. output
frequency
240 Hz 200 Hz