Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C converter
38 Getting Started, 04/2014, FW V4.7, A5E34264105B AA
Directly select the parameter number
The BOP-2 offers the possibility of setting the parameter number digit by digit.
Precondition
The parameter number is flashing in the BOP-2 display.
Procedure
To select the parameter number directly, proceed as follows:
1.
Press the OK button for longer than five seconds.
2.
Change the parameter number digit-by-digit.
If you press the OK button then the BOP-2 jumps to the next digit.
3.
If you have entered all of the digits of the parameter number, press the
OK button.
You have now entered the parameter number directly.
Entering the parameter value directly
The BOP-2 offers the option of setting the parameter value digit by digit.
Precondition
The parameter value flashes in the BOP-2 display.
Procedure
To select the parameter value directly, proceed as follows:
1.
Press the OK button for longer than five seconds.
2.
Change the parameter value digit-by-digit.
If you press the OK button then the BOP-2 jumps to the next digit.
3.
If you have entered all of the digits of the parameter value, press the
OK button.
You have now entered the parameter value directly.
When must you not change a parameter?
The converter indicates why it currently does not permit a parameter to be changed:
You have attempted to change
a read-only parameter.
You must change to basic
commissioning to set this
parameter.
You must turn the motor
off to set this parameter.
The operating state in which you can change a parameter is provided in the List Manual for
each parameter.