Fault rectification
5.1 List of alarms and faults
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
63
Number
Cause
Remedy
F08700 Communications error A CAN communications error has occurred. Check the following:
Bus cable
Baud rate (p8622)
Bit timing (p8623)
Master
Start the CAN controller manually with p8608 = 1 after the cause of the fault
has been resolved!
F13100 Know-how protection: Copy
protection error
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy
protection cannot be activated
Insert a valid memory card.
F30001 Overcurrent Check the following:
Motor data, if required, carry out commissioning
Motor's connection method (Υ / Δ)
U/f operation: Assignment of rated currents of motor and Power Module
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
F30002 DC-link voltage overvoltage Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
F30003
DC-link voltage undervoltage
Check the line voltage (p0210).
F30004 Converter overtemperature Check whether the converter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
F30005 I2t converter overload Check the rated currents of the motor and Power Module.
Reduce current limit p0640.
When operating with U/f characteristic: Reduce p1341.