Connecting up, switching on
4.2 Line, motor and DC link connection
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
33
Table 4- 3 Maximum cable lengths
Shielded cable, devices without
100 m --
Unshielded cable, devices without
output filter
200 m --
Shielded cable, devices with out-
put filter
Output reactor, du/dt filter
Unshielded cable, devices with
output filter
Output reactor, du/dt filter
Motor connection
Star and delta connection
Siemens motors have a diagram inside
the terminal box showing both connection
met
hods:
Star connection (Y)
Delta connection (Δ)
The motor rating plate provides data about the
correct connection.
Connecting the motor to the converter
Connect the protective conductor of the motor to the terminal of the converter.
Connect the motor cable to terminals U2, V2 and W2.
If available, close the terminal covers of the converter.