Technical specifications
6.1 General technical data
Power Module PM330
66 Hardware Installation Manual, 10/2016, A5E32844552B AD
Table 6- 1 General technical data
Line system configurations Grounded TN/TT systems or ungrounded IT systems (a grounded phase conductor is not
permissible in 690 V line supplies)
Line requirement A line reactor (2% u
k
) must be connected in series
Line voltage 380 V (-10 %) ... 480 V (+10 %)
500 V (-10 %) ... 690 V (+10 %)
Displacement factor cos φ
0.96
0.75 ... 0.93 (with line reactor u
k
= 2%)
Short-circuit current rating
according to IEC, in conjunc-
tion with the specified fuses
160 ... 630 kW: 100 kA
Short-circuit current rating
according to UL61800-5-1
(up to 480 V AC or 600 V
AC), in conjunction with the
160 ... 630 kW: 100 kA
Can be used on line supplies that cannot supply more than 100 kA symmetrically at a max-
imum voltage of 480 V AC or 600 V AC when they are protected with the semiconductor
fuses specified in Chapter "Technical Data" of this manual.
III according to EN 61800-5-1
Protection class according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Forced air cooling AF according to EN 60146
Sound pressure level L
PA
(1
≤ 74 dB(A)
1)
according to EN 61800-5-1: For the intended purpose
Compliance with standards
Standards EN 60146-1-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529
UL61800-5-1, CSA 22.2 No. 274-13
CE marking In accordance with EMC Directive No. 2014/30/EU and Low-Voltage Directive
Radio interference suppres-
In accordance with the EMC product standard for variable-speed drives EN 61800-3, "sec-
2)
. Application in "first environment" possible with line filters.
cULus (File No.: E192450), CE, RCM, EAC, KC