Technical specifications
6.1 General technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
67
3)
3)
Ambient temperature -25° … +55° C -25 ... +70 °C
0°
... +40° C
up to + 50° C with derating
Relative humidity
(no condensation)
5 to 95%
5 ... 95% at 40° C
5 ... 95%
Environmental class /
harmful chemical substances
1C2 acc. to EN 60721-3-1 2C2 acc. to EN 60721-3-2 3C2 acc. to EN 60721-3-3
Organic/biological influences
2 according to EN 61800-5-1
Installation altitude up to 1000 m above sea level without derating,
> 1000 m above sea level with derating (see Chapter Derating as a function of the installa-
3)
3)
Vibrational load
- Displacement
- Acceleration
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to
EN 60068-2-6
0.075 mm for 10 ... 58 Hz
9.81 ma/s² (1 x g) at > 58 ...
Shock load
- Displacement
- Acceleration
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Test according to EN 60068-
2-27 (EA shock type)
49 ma/s² (5 x g)/30 ms
147 m/s² (15 x g)/11 ms
Deviations from the defined classes are shown in
italics
.
maximum sound pressure level, ascertained in the IP20 cabinet
Standard construction: Devices installed in the control cabinet with installation in conformance with EMC regulations,
line reactor uk = 2%, shielded motor cable (e.g. Protoflex EMC) with max. 100 m cable length,
line harmonics according to EN 61000-2-4: Class 2, THD(U) total = 8% for typical line conditions (RSC > 30 ... 50);
THD(I) total: typically 30 … 45 % (15 < RSC < 50)
3)
in transport packaging