Technical specifications
6.3 Derating data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
85
Table 6- 9 Derating of the output current as a function of the line voltage, 3 AC 500 V … 690 V
Rated output current I
N
at
500 V/690 V
6SL3310-1PG34-0AA0 400 A / 393 A 100% 99.3% 99.0% 98.6% 98.3%
Derating of the output current as a function of the pulse frequency
With the factory setting, the drive starts with a 4 kHz pulse frequency, and under load,
automatically reduces the pulse frequency step-by-step to the frequencies required. When
the load decreases, the pulse frequency is increased automatically up to 4 kHz.
The values of the rated current apply to a pulse frequency of 2 kHz at 40° C ambient
temperature and are reached at any time by the automatic adaptation of the output pulse
frequency.