Connecting up, switching on
4.7 Switching on
Power Module PM330
56 Hardware Installation Manual, 10/2016, A5E32844552B AD
4.7
Switching on
The converter is switched on in the following steps:
Switch on the line voltage
The power supply inside the converter switches on,
the DC link is still not precharged.
Switch on the converter at the operator panel or with STARTER
By issuing the ON/OFF command (ON button at the IOP or p0840 = 1 using
STARTER).
The DC link is now precharged (this takes approx. 4 s).
Start the converter
depending on the parameter assignment, the inverter pulses must be separately enabled -
and the converter then accelerates the motor up to the selected speed.