EasyManua.ls Logo

Siemens SINAMICS G120P PM330 - Page 55

Siemens SINAMICS G120P PM330
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting up, switching on
4.6 EMC compliant connection
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
55
Additional measures
Finely stranded, braided copper cables have to be routed in parallel with the cable shields in
the following cases:
Old installations with existing unscreened cables
Cables with poor high-frequency properties of the shield
Installations with bad grounding systems
Connections shown in the following diagram offer a durable, high-frequency equipotential
bonding between the motor enclosure, the motor terminal box, the driven load and the EMC
rail/busbar.
Figure 4-15 Additional high-frequency bonding of the drive system

Table of Contents

Related product manuals