Connecting up, switching on
4.3 Operation on a non-grounded line supply (IT system)
Power Module PM330
40 Hardware Installation Manual, 10/2016, A5E32844552B AD
Figure 4-4 Open the connection to the interference suppression module
The connection is opened as follows:
1. Release the left-hand housing flap by rotating latch
and opening the housing flap.
2. Release the two screws
; they are captive.
3. Release screws
, and , but do not remove the screws.
4. Swivel the connection clip
around the axis of rotation of screw towards the left, until
the connection clip can be fastened using screw
.
5. Tighten the screws
, and with 6 Nm.