91
Category C2
First environment - commercial use
Power Modules with additional line filter
fulfill the requirements relating to cable-conducted noise interference emission
(interference), if
a shielded cable with low capacitance is used,
the current does not exceed the rated input current (see Specific technical data
(Page 70)),
the pulse frequency does not exceed 4 kHz, and
the cable is not longer than 100 m.
can cause high-frequency disturbances. In this case, damping measures may be required
in order that the requirements relating to radiated noise interference can be fulfilled.
Note
Devices for use in Category C2
first environment, commercial use must be installed by a
specialist with the appropriate experience fo
r installing and/or commissioning power drive
systems, including their EMC aspects.
Category C2
Second environment
Power Modules with additional line filter
fulfill the requirements relating to cable-conducted noise interference emission
(interference), if
a shielded cable with low capacitance is used
the current does not exceed the rated input current (see Specific technical data
(Page 70)),
the pulse frequency does not exceed 4 kHz, and
the cable is not longer than 100 m.
can cause high-frequency disturbances. In this case, damping measures may be required
in order that the requirements relating to radiated noise interference can be fulfilled.
Category C3
Second (industrial) environment
Power Modules can be installed without any restrictions in Category C3 second
environment and do not require any authorization for connection.
EMC / Immunity
The Power Modules have been tested in accordance with the immunity requirements of
category C3 - Second Environment - and fulfill the requirements according to EN 61800-3.
Note
The immunity requirements apply equally to both filtered and unfiltered Power Modules.