List of messages
Display messages
05/2020, 4BS0576F-004
11
Text for event memory entry
2095 !! Prewarning !! T-cooler 4 too high Wrg>T-Cool.4 t.hi Temperature at the dissipator 4 too high prewarning temperature depend-
ing on the device). Cool down the operating environment; reduce the load;
clean the air filter; recheck the fan
2096 !! Prewarning !! T-cooler 5 too high Wrg>T-Cool.5 t.hi Temperature at the dissipator 5 too high prewarning temperature depend-
ing on the device). Cool down the operating environment; reduce the load;
clean the air filter; recheck the fan
2100 !! Prewarning !! Current asymmetry U Wrg>C-Asymm. U - This warning can appear only with inverters having several converter sys-
tems connected in parallel, if in the U-phase the current of one system
deviates from the mean value by more than 10%. Recheck if the motor
conductors are arranged symmetrically, if all motor connections are cor-
rectly put on and tightened. If you find no incorrectness's please inform our
service station.
2101 !! Prewarning !! Current asymmetry V Wrg>C-Asymm. V - This warning can appear only with inverters having several converter sys-
tems connected in parallel, if in the V-phase the current of one system
deviates from the mean value by more than 10%. Recheck if the motor
conductors are arranged symmetrically, if all motor connections are cor-
rectly put on and tightened. If you find no incorrectness's please inform our
service station.
2102 !! Prewarning !! Current asymmetry W Wrg>C-Asymm. W - This warning can appear only with inverters having several converter sys-
tems connected in parallel, if in the W-phase the current of one system
deviates from the mean value by more than 10%. Recheck if the motor
conductors are arranged symmetrically, if all motor connections are cor-
rectly put on and tightened. If you find no incorrectness's please inform our
service station.
2103 !! Prewarning !! T-heat sink asymm. Wrg>T-Cooler asym - The distribution of temperature on the power heatsink is asymmetrical.
Check the air intake filter for dirt resp. Check the fan of the device.
2104 !! Prewarning !! T-CPU too low Wrg>T-CPU too low - Temperature inside the inverter too low
(warning given at 0°C). Heat up the
operating environment. Temperature inside the inverter too high (prewarn-
ing at 70°C). Cool down the operating environment; reduce the load; clean
the air filter; recheck the fan
2105 !! Prewarning !! T-CPU too high Wrg>T-CPU too hi Temperature inside the cabinet too high prewarning temperature at 70°C).
Cool down the operating environment; reduce the load; clean the air filter;
recheck the fan
2106 !! Prewarning !! T-cooler too high Wrg>T-Cool. t.hi - Temperature at the dissipator too high prewarning temperature depending
on the device). Cool down the operating environment; reduce the load;
clean the air filter; recheck the fan
2107 !! Prewarning !! T-cooler too low Wrg>T-Cool. t.lo - Temperature at the measuring point of the dissipator too low (warning at
0°C). Heat up the operating environment;