List of messages
Display messages
12 05/2020, 4BS0576F-004
Text for event memory entry
2108 !! Prewarning !! T-cooler 1 too low Wrg>T-Cool.1 t.lo Temperature at the measuring point 1 of the dissipator too low (warning at
0°C). Heat up the operating environment;
2109 !! Prewarning !! T-cooler 1 too high Wrg>T-Cool.1 t.hi Temperature at the dissipator 1 too high prewarning temperature depend-
ing on the device). Cool down the operating environment; reduce the load;
clean the air filter; recheck the fan
2110 !! Prewarning !! Brake Res.Overload Wrg>BrakeResOverl - Brake resistor overloaded. Reduce the regenerative load; use a brake
resistor with a higher rating; line voltage too high (> 110%)
2112 !! Prewarning !! PTC AI1 Wrg>PTC AI 1 - This message can appear only if the analog input 1 is configured for ther-
mistor evaluation. P-ANALOG INPUT/P-Analog input 1:AI-function = PTC.
It is active when the thermistor has tripped. Recheck the PTC-sensor at
terminal –X2:51-52. Recheck the device where the thermistor is installed.
2113 !! Prewarning !! PTC AI2 Wrg>PTC AI 2 - This message can appear only if the analog input 2 is configured for ther-
mistor evaluation. "P-ANALOG INPUT/P-Analog input 2:AI-function =
PTC". It is active when the thermistor has tripped. Recheck the PTC-
sensor at terminal –X2:51-53. Recheck the device where the thermistor is
installed.
2114 !! Prewarning !! InputReactor 1 Wrg>InptReactor1 - The temperature of the input reactor of the device has nearly reached the
cutoff limit. Clean the air filter; recheck the fan of the device; recheck the
temperature contact in the reactor: input at PCB Signals –A13-X81:6:
24V=good, 0V=warning. Reduce the load; cool down the operating envi-
ronment.
2115 !! Prewarning !! OutputReactor 1 Wrg>OutptReactor1 - The temperature of the output reactor of the device has nearly reached the
cutoff limit. Clean the air filter; recheck the fans of the device; recheck the
temperature contact in the reactor: input at PCB Signals –A13-X81:7:
24V=good, 0V=warning; reduce the load; cool down the operating envi-
ronment;