List of messages
Display messages
14 05/2020, 4BS0576F-004
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
2118 !! Prewarning !! P-Warning 3/T= as no. 2116 as no. 2116 - P-Warning 3: as no. 2116
2119 !! Prewarning !! P-Warning 4/T= as no. 2116 as no. 2116 - P-Warning 4: as no. 2116
2120 !! Prewarning !! P-Warning 5/T= as no. 2116 as no. 2116 - P-Warning 5: as no. 2116
2121 !! Prewarning !! P-Warning 6/T= as no. 2116 as no. 2116 - P-Warning 6: as no. 2116
2122 !! Prewarning !! P-Warning 7/T= as no. 2116 as no. 2116 - P-Warning 7: as no. 2116
2123 !! Prewarning !! P-Warning 8/T= as no. 2116 as no. 2116 - P-Warning 8: as no. 2116
2124 !! Prewarning !! P-Warning 9/T= as no. 2116 as no. 2116 - P-Warning 9: as no. 2116
2125 !! Prewarning !! P-Warning 10/T= as no. 2116
as no. 2116 - P-Warning 10: as no. 2116
2126 !! Prewarning !! P-Warning 11/T= as no. 2116
as no. 2116 - P-Warning 11: as no. 2116
2127 !! Prewarning !! P-Warning 12/T= as no. 2116
as no. 2116 - P-Warning 12: as no. 2116
2128 !! Prewarning !! P-Warning 13/T= as no. 2116
as no. 2116 - P-Warning 13: as no. 2116
2129 !! Prewarning !! P-Warning 14/T= as no. 2116
as no. 2116 - P-Warning 14: as no. 2116
2130 !! Prewarning !! P-Warning 15/T= as no. 2116
as no. 2116 - P-Warning 15: as no. 2116
2131 !! Prewarning !! P-Warning 16/T= as no. 2116
as no. 2116 - P-Warning 16: as no. 2116
2132 !! Prewarning !! P-Warning 17/T= as no. 2116
as no. 2116 - P-Warning 17: as no. 2116
2133 !! Prewarning !! P-Warning 18/T= as no. 2116
as no. 2116 - P-Warning 18: as no. 2116
2134 !! Prewarning !! P-Warning 19/T= as no. 2116
as no. 2116 - P-Warning 19: as no. 2116
2135 !! Prewarning !! P-Warning 20/T= as no. 2116
as no. 2116 - P-Warning 20: as no. 2116
2136 !! Prewarning !! Thermistor X3:92/93 Wrg>PTC X3:92/93 - Only if OPTION Periphery 2 or 4 available. Thermistor input at terminal
X3:92/93 has tripped. Device (usually the motor) is overloaded; reduce the
load PTC-sensor of which is connected to terminal –X3:92/93, recheck.
2137 !! Prewarning !! T-rectifier too low Wrg>T-rect.t.low - Temperature at dissipator (measuring point rectifier) too low (tripping at
0°C). Heat up the operating environment;
2138 !! Prewarning !! T-rectifier too high Wrg>T-rect.t.high - Temperature at dissipator (measuring point rectifier) too high. Cool down
the operating environment; reduce the load; clean the air filter; recheck the
fan of the device
2139 !! Prewarning !! T-cabinet too high Wrg>T-cab.t.high - Temperature at air intake of control cabinet too high. Cool down the operat-
ing environment; reduce the load; clean the air filter; recheck the fan of the
device
2144 !! Prewarning !! Fault Synch. LSC Wrg>Synch. LSC If several inverters drive a motor/generator, all inverters must be synchro-
nized. To this all inverters are linked via fiber optic cable, connected on
PCB LSC -A51. Chec
k this fiber optic cable connection. Check whether the
parameters are the same in P-Mains power conv. at all inverters.