List of messages
Display messages
05/2020, 4BS0576F-004
23
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
3032 !! Inverter fault !! InputReactor 2 IF>InpReactor 2 low/ mean The temperature of the input reactor L8.2 is too high. Clean the air filter;
recheck the fans of the device. Recheck the temp. contact of the reactor:
input at PCB Signals –A13-X81:15: 24V=good, 0V=fault.
Cool down the operation environment.
3033 !! Inverter fault !! OutputReactor 1 IF>OutpReactor 1 low/ mean The temperature of the output reactor L1 (L1.1) is too high. Clean the air
filter; recheck the fans of the device. Recheck the temp.contact of the
reactor: input at PCB Signals –A13-X81:12: 24V=good, 0V=fault.
Cool down the operation environment; measure the length of the motor
conductors, note the type of the motor conductors and contact our service
station. Maybe the motor conductors are too long for the installed filter.
3034 !! Inverter fault !! OutputReactor 2 IF>OutpReactor 2 low/ mean The temperature of the output reactor L1.2 is too high. Clean the air filter;
recheck the fans of the device. Recheck the temp.contact of the reactor:
input at PCB Signals –A13-X81:11: 24V=good, 0V=fault. Cool down the
operation environment; measure the length of the motor conductors, note
the type of the motor conductors and contact our service station.
Maybe the motor conductors are too long for the installed filter.
3035 !! Inverter fault !! I2C-Bus IF>I2C-Bus - The inverter-internal I2C-bus is defective. Contact our service station.
3036 !! Inverter fault !! EarthCurrentMetering IF>I-EarthMeter. low Summation current transformer –T20 not plausible. Check the cable to the
current transformer. Contact our service station.
3037 !! Inverter fault !! Ter. X81:13 inactiv IF>X83:13 inactiv - By standard this input is not assigned. Check the documentation which
monitoring is assigned to input –X81:13 of PCB Signals –A13. 24V=good,
0V=fault
3038 !! Inverter fault !! Ter. X81:14 inactiv IF>X83:14 inactiv - By standard this input is not assigned. Check the documentation which
monitoring is assigned to input –X81:14 of PCB Signals –A13. 24V=good,
0V=fault
3039 !! Inverter fault !! Test safe torque off IF>Test STO - 1. The test of the two shut down paths for safe standstill results in a fault.
Always contact our service station as this involves a safety-relevant func-
tion. See also the inverter description 4BS0751, Chapter Options, board
I/O.
2. You have set switch S3 on board I/O DI/DO to single-circuit trip and
parameter "P-INVERTER DATA:STO" to two-circuit trip. Terminal input -
X2:24 is simultaneously deactivated. Correct the setting.
(NOTICE!: safety-related function)
3040 !! Inverter fault !! Test PTC X3:90/91 IF>Test X3:90/91 - One of the two disconnection paths for safe halt is defective. As it is a
safety relevant function please do contact our service station. See also the
description of the inverter 4BS0751, chapter Options, PCB Peripherals
3044 !! Inverter fault !! PerformParameters IF>PerformParam - Hardware fault PCB Control electronics or PCB Current control. Contact
our service station.