List of messages
Display messages
24 05/2020, 4BS0576F-004
Text for event memory entry
3060 !! Fault !! Interr. RS485 (X26) Flt>RS485 (X26) The fault occurs if:
- the external display is not correctly connected to the RS485 interface
-X26 or if it is disconnected
- at "P-INTERFACES/P-RS485(X26)=failure" is set and
- a RS485 setpoint source is parameterized. If there is an external display
at the RS485-interface –X26, connect / commission as per description,
chapter Communication / External display.
If there is no external display, recheck the parameter setting in menus
"P-SPEED DEFAULT, PROCESS CONTROL, CONTROL, CURRENT
CONTROL/..Setpoint source". If a parameter is on RS485 or, under
"P-OPERATION", if a parameter is on …..ext.Bdf relocate these parame-
ters to another source.
3061 !! Fault !! Diff. current motor Flt>I-diff. Motor The difference current supervision in the inverter has tripped. An earth
current more than at "P-INVERTERDATA/P-monitoring/I-earth MSR" is
flowing. Check where the earth fault is located. The earth fault can be
located either in the inverter, downstream converter current transformers,
in the motor conductors or in the motor.
Possibly, the parameter "I-earth MSR" con adjusted to a higher level.
In this case contact our service station.
3075 !! Fault !! T-cabinet too low Flt>T-cab.t.low Temperature at air intake of control cabinet too low (trip at -5°C). Heat up
the operating environment;
3077 !! Fault !! T-cooler 2 too high Flt>T-Cool.2 t.hi Temperature at dissipator 2 too high (cut-off temp. depending on the de-
vice). Cool down the operation environment; reduce the load; clean the air
filter; recheck the fan of the device.
3078 !! Fault !! T-cooler 3 too high Flt>T-Cool.3 t.hi Temperature at dissipator 3 too high (cut-off temp. depending on the de-
vice). Cool down the operation environment; reduce the load; clean the air
filter; recheck the fan of the device.
3079 !! Fault !! T-cooler 4 too high Flt>T-Cool.4 t.hi Temperature at dissipator 4 too high (cut-off temp. depending on the de-
vice). Cool down the operation environment; reduce the load; clean the air
filter; recheck the fan of the device.
3080 !! Fault !! T-cooler 5 too high Flt>T-Cool.5 t.hi Temperature at dissipator 5 too high (cut-off temp. depending on the de-
vice). Cool down the operation environment; reduce the load; clean the air
filter; recheck the fan of the device.
3081 !! Fault !! T-cooler 1 too low Flt>T-Cool.1 t.lo Temperature at dissipator 1 too low (cut-off at -5° C).
Heat up the operation environment;
3082 !! Fault !! T-cooler 2 too low Flt>T-Cool.2 t.lo Temperature at dissipator 2 too low (cut-off at -5° C).
Heat up the operation environment;
3083 !! Fault !! T-cooler 3 too low Flt>T-Cool.3 t.lo Temperature at dissipator 3 too low (cut-off at -5° C).
Heat up the operation environment;