3453 !! OFF 2 !! Contr. AD missing OFF2>contr. AD - This error occurs when under "P-INTERFACE/P-Fieldbus/Contr. AD" the
parameterized bit in the control word is not specified by your control, the
reaction under "P-INTERFACE/P-Fieldbus/Rct. BUS = Fault" is parameter-
ized and a setpoint, the actual value or the operating source are parame-
terized to BUS. If you have a BUS interface in the device, set the
corresponding control word bit of your control to 1. If you do not have a
BUS interface in your control, then check the parameterization of "P-
INTERFACE/Op.-source=BUS" or "Reset source=BUS" or the setpoint
sources in the menus of the control modes (e.g. "P-speed default, P-
process control, …").
BUS may not be actively selected here.
3454 !! OFF 2 !! Interruption RS485 OFF2>InterrpRS485 - The fault occurs if:
- the external display is not correctly connected to the RS485 interface or if
it is disconnected
- at "P-INTERFACES/P-RS485/RktRS485=failure" is set and
- a RS485 setpoint source is parameterized.
If there is an external display at the RS485-interface –X51, connect / com-
mission as per description 4BS0751, chapter Communication / External
display.
If there is no external display, recheck the parameter setting in menus
"P-speed default, P-process control, P-T-control, P-current
control:..Setpoint source". If a parameter is on "RS485" or, under
"P-OPERATION", if a parameter is on "…..ext.Bdf" relocate these parame-
ters to another source.
3455 !! OFF 2 !! Interr. RS485 (X26) OFF2>IntRS485 X26 The fault occurs if:
- the external display is not correctly connected to the RS485 interface or if
it is disconnected
- at "P-INTERFACES/P-Fieldbus/Rct.BUS=failure is set and
- a RS485 setpoint source is parameterized.
If there is an external display at the RS485-interface –X51, connect / com-
mission as per description 4BS0751, chapter Communication / External
display.
If there is no external display, recheck the parameter setting in menus
"P-speed default, P-process control, P-T-control, P-current
control:..Setpoint source". If a parameter is on "RS485" or, under
"P-OPERATION", if a parameter is on "…..ext.Bdf" relocate these parame-
ters to another source.
3461 !! Emergency stop !! Interruption BUS ESt>Interrpt.BUS - As message no. 3451,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=fast stop" parameterized
3462 !! Emergency stop !! BUS Hardware ESt>BUS Hardware - As message no. 3452,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=Emergency stop" parameterized